Power system balancing with high renewable penetration : the potential of demand response
Name
793105210-MIT.pdf
Description
Full printable version
Size
12.71 MB
Format
Adobe PDF
Checksum (MD5)
d5110ccf65f17075555bebe84ffbd977
Author(s)
Critz, David Karl
Advisor(s)
Stephen Connors.
Date Issued
2012
Publisher
Massachusetts Institute of Technology
Abstract
This study investigated the ability of responsive demand to stabilize the electrical grid when intermittent renewable resources are present. The WILMAR stochastic unit commitment model was used to represent a version of the Danish electricity and heat system with an enhanced level of wind generation. The study found that demand response reduced the marginal operating cost of the electrical system 3%. Demand response reduced CO₂ /SO₂ emissions levels 3% by enabling 11% more generation of wind power. Demand resources representing 25% of nameplate wind power and priced at 150% of a gas turbine's marginal cost were a recommended combination that balanced maximum system improvement at minimal ratepayer impact. The system cost benefits of each study case enabled the calculation of a demand curve representing the system operator's willingness to pay fixed costs for capacity from the pool of operating savings. With demand response, wind generators increased profits, coal plants reduced profits slightly, and natural gas plant profit was cut to almost zero. With high levels of unpredictable renewable resources and limited ability to import power, demand response represents a promising technique to balance the grid at low cost.
Description
Thesis (S.M. in Engineering and Management)--Massachusetts Institute of Technology, Engineering Systems Division, February 2012.
"September 2011." Cataloged from PDF version of thesis.
Includes bibliographical references (p. 61-62).
Subjects
Engineering Systems Division.
System Design and Management Program.
MIT Department
System Design and Management Program.
Massachusetts Institute of Technology. Engineering Systems Division
Terms of Use
M.I.T. theses are protected by
copyright. They may be viewed from this source for any purpose, but
reproduction or distribution in any format is prohibited without written
permission. See provided URL for inquiries about permission.
copyright. They may be viewed from this source for any purpose, but
reproduction or distribution in any format is prohibited without written
permission. See provided URL for inquiries about permission.
Persistent DSpace Link