Electric Arc Holes in Corrugated Stainless Steel Tubing
Name
10694_2017_663_ReferencePDF.pdf
Size
1.91 MB
Format
Adobe PDF
Checksum (MD5)
b263db432a4483cfce0ab4f435c8e418
Author(s) • •
Taylor, Richard
Larson, Harold R
Eagar, Thomas W
Date Issued
June 2017
Journal
Fire Technology
Publisher
Springer-Verlag
Citation
Taylor, Richard H. et al. “Electric Arc Holes in Corrugated Stainless Steel Tubing.” Fire Technology 53, 5 (June 2017): 1919–1932 © 2017 Springer Science+Business Media New York
Version
Author's final manuscript
Abstract
Corrugated stainless steel tubing (CSST) has become a common product installed in new and retrofitted older homes. The ease of installation due to its flexibility and the need for fewer joints significantly lowers labor costs. Despite the advantages of lower cost and ease of installation, however, the thin wall of CSST presents an increased risk of perforation by both mechanical puncturing and electrical arcing from either household current or lightning strikes. In the course of forensic investigations of household fires, perforated tubing is occasionally identified as a potential cause. The metallurgical features of the perforated area are capable of distinguishing the cause of the hole as being from either lightning current or household current.
MIT Department
MIT Materials Research Laboratory
Massachusetts Institute of Technology. Department of Materials Science and Engineering
Terms of Use
Creative Commons Attribution-Noncommercial-Share Alike
Persistent DSpace Link
DOI of Published Version
http://dx.doi.org/10.1007/s10694-017-0663-1