Unique airflow visualization techniques for the design and validation of above-plenum data center CFD models
Name
665842351-MIT.pdf
Description
Full printable version
Size
18.24 MB
Format
Adobe PDF
Checksum (MD5)
8f06a455a4b1be9479051b22ebf16c11
Author(s)
Lloyd, Michael David, S.M. Massachusetts Institute of Technology
Advisor(s)
Leon R. Glicksman.
Date Issued
2010
Publisher
Massachusetts Institute of Technology
Abstract
One cause for the substantial amount of energy used for data center cooling is poor airflow effects such as hot-aisle to cold-aisle air recirculation. To correct these and to investigate innovative designs that will notably increase efficiency requires a robust, well-verified computational fluid dynamics (CFD) model. Most above-plenum data center CFD models are only validated using temperature data. Although a temperature-only validation method can be useful, it does not confirm that the airflow patterns predicted by the CFD model are accurate. Since the airflow patterns above a raised-floor plenum should be confidently understood before they can be optimized, it is necessary to adopt a validation method that offers more than just a comparison of temperature data. This thesis summarizes the unique validation process of a CFD model for a small data center test cell located in Cambridge, Massachusetts. The validation method features point velocity and temperature measurements and the use of small neutrally-buoyant bubbles to visualize the airflow patterns above a raised-floor plenum. The data center test cell was designed to emulate a standard hot-aisle and cold-aisle airflow configuration. The airflow visualization revealed that each perforated tile had a substantial nonuniform air velocity distribution leading to an unexpected three-dimensional flow pattern above the racks. When this surprising reality was properly accounted for in the CFD boundary conditions, good agreement was found with the observed airflow patterns. It is the purpose of this thesis to show the difficulties and value of utilizing more robust validation techniques for data center CFD models.
Description
Thesis (S.M.)--Massachusetts Institute of Technology, Dept. of Architecture, 2010.
Includes bibliographical references (p. 119-121).
Subjects
Architecture.
MIT Department
Massachusetts Institute of Technology. Department of Architecture
Terms of Use
M.I.T. theses are protected by
copyright. They may be viewed from this source for any purpose, but
reproduction or distribution in any format is prohibited without written
permission. See provided URL for inquiries about permission.
copyright. They may be viewed from this source for any purpose, but
reproduction or distribution in any format is prohibited without written
permission. See provided URL for inquiries about permission.
Persistent DSpace Link