Energy, power, and office buildings : design and analysis of an off-peak cooling system using structural mass storage

Thumbnail Image
Download
Name

08995792-MIT.pdf

Description
Full printable version
Size

12.75 MB

Format

Adobe PDF

Checksum (MD5)

bd7de861c8fa57fe5d05b2d0e10b8978

Author(s)
Mathis, Rory Christopher
Advisor(s)
Timothy E. Johnson.
Date Issued
1982
Publisher
Massachusetts Institute of Technology
Abstract
As the electric utilities face ever increasing peak power production requirements, (mostly from the commercial sector) scheduled "time-of-day" pricing schemes have become imperative. At present, most conservation strategies for commercial buildings focus on the reduction of energy consumption orchestrated (justifiably) by t he expense of electrical energy for lighting and cooling which dominate their loads. However, these conservation schemes, such as higher efficiency lamps, various glazing techniques, etc., do not alter the time of consumption nor do they utilize the lower off-peak electrical rates. The results are as before; high energy costs due to peak (daytime) consumption, and projected savings from the various conservation strategies are overshadowed or not realized. This thesis investigates a decentralized off-peak cooling system for commercial office buildings utilizing the structural mass as the thermal storage medium. The system incorporates an exposed concrete ceiling slab cooled at night with imbedded chilled water pipes and taking full advantage of off-peak electrical rates. The ceiling/slab - waterpipe system is modeled via two-dimensional finite difference methods for transient analysis. The sensitivity of the system to pipe size and spacing, internal loads, water temperatures, and surface geometry is assessed. The analytical results suggest the potential for application, however, additional research must be undertaken to investigate the economic implications of fabrication and to more adequately determine the effects of non-planar surface geometry.
Description
Thesis (M.S.)--Massachusetts Institute of Technology, Dept. of Architecture, 1982.
MICROFICHE COPY AVAILABLE IN ARCHIVES AND ROTCH.
Includes bibliographical references.
Subjects
Architecture.
MIT Department
Massachusetts Institute of Technology. Department of Architecture
Terms of Use
M.I.T. theses are protected by
copyright. They may be viewed from this source for any purpose, but
reproduction or distribution in any format is prohibited without written
permission. See provided URL for inquiries about permission.
http://dspace.mit.edu/handle/1721.1/7582
Persistent DSpace Link
http://hdl.handle.net/1721.1/75913
Repository logo
PrivacyPermissionsAccessibilityContact us
Repository logo
Notify us about copyright concerns.