A Simple Technique for Islanding Detection with Negligible Nondetection Zone
Name
Zeineldin-2009-A Simple Technique for Islanding Detection With Negligible Nondetection Zone.pdf
Size
455.64 KB
Format
Adobe PDF
Checksum (MD5)
db1bb79fbee89568aaa050c057afd216
Date Issued
March 2009
Journal
IEEE Transactions on Power Delivery
Publisher
Institute of Electrical and Electronics Engineers (IEEE)
Citation
Zeineldin, H.H., and J.L. Kirtley. “A Simple Technique for Islanding Detection With Negligible Nondetection Zone.” IEEE Transactions on Power Delivery 24.2 (2009): 779–786. © Copyright 2009 IEEE
Version
Final published version
Abstract
Although active islanding detection techniques have smaller nondetection zones than passive techniques, active methods could degrade the system power quality and are not as simple and easy to implement as passive methods. The islanding detection strategy, proposed in this paper, combines the advantages of both active and passive islanding detection methods. The distributed-generation (DG) interface was designed so that the DG maintains stable operation while being grid connected and loses its stability once islanded. Thus, the over/undervoltage and over/underfrequency protection method would be sufficient to detect islanding. The main advantage of the proposed technique is that it relies on a simple approach for islanding detection and has negligible nondetection zone. The system was simulated on PSCAD/EMTDC and simulation results are presented to highlight the effectiveness of the proposed technique.
MIT Department
Massachusetts Institute of Technology. Department of Electrical Engineering and Computer Science
Terms of Use
Article is made available in accordance with the publisher's policy and may be subject to US copyright law. Please refer to the publisher's site for terms of use.
Persistent DSpace Link
DOI of Published Version
https://doi.org/10.1109/TPWRD.2009.2013382