A Retrofit 60 Hz Current Sensor for Power Monitoring at the Circuit Breaker Panel
Name
Leeb_A retrofit 60 Hz.pdf
Size
956.53 KB
Format
Adobe PDF
Checksum (MD5)
0e2659bdb4a3c9ede248bba1fb63f796
Author(s) • • • •
Cooley, John J.
Vickery, Daniel R.
Avestruz, Al-Thaddeus
Clifford, Zachary
Leeb, Steven B.
Date Issued
September 2010
Journal
Proceedings of the IEEE 12th Workshop on Control and Modeling for Power Electronics (COMPEL), 2010
Publisher
Institute of Electrical and Electronics Engineers (IEEE)
Citation
Cooley, John J. et al. “A Retrofit 60 Hz Current Sensor for Power Monitoring at the Circuit Breaker Panel.” Proceedings of the IEEE 12th Workshop on Control and Modeling for Power Electronics (COMPEL), 2010. 1–7.
Version
Final published version
Abstract
Improved signal conditioning electronics and new experimental results are presented for a sensor that measures current flow in a circuit breaker. A PIC microcontroller optimizes the phase reference for the synchronous detection system on startup eliminating the need for I/Q demodulation. Ultimately, the parts count of the signal conditioning electronics is halved compared to the previous work. Experimental results are presented demonstrating the sensor's response to 60 Hz signals with higher harmonic content and to step transients in 60 Hz signal amplitudes. The proposed current sensor does not require permanent modification of the breaker panel or the circuit breaker itself. The intent of this work is to develop a low-cost, non-intrusive, retrofit sensor for centralized power monitoring at the circuit breaker.
MIT Department
Massachusetts Institute of Technology. Department of Electrical Engineering and Computer Science
Terms of Use
Article is made available in accordance with the publisher's policy and may be subject to US copyright law. Please refer to the publisher's site for terms of use.
Persistent DSpace Link
DOI of Published Version
https://doi.org/10.1109/COMPEL.2010.5562435