Repository logo
Log in(current)
Repository logoMIT Open ScholarshipDSpace@MIT
  1. Home
  2. MIT Open Access Articles
  3. MIT Open Access Articles
  4. Analytical and Experimental Studies on the Hybrid Fault Current Limiter Employing Asymmetric Non-Inductive Coil and Fast Switch

Analytical and Experimental Studies on the Hybrid Fault Current Limiter Employing Asymmetric Non-Inductive Coil and Fast Switch

Thumbnail Image
Download
Name

Park-2009-Analytical and Exper.pdf

Size

606.53 KB

Format

Adobe PDF

Checksum (MD5)

70519fc413163a3f70b7f422a066ea1e

Author(s)
Yang, Seong Eun
•
Yoon, Yong Soo
•
Kim, Ho Min
•
Park, Jung-Wook
•
Ko, Tae Kuk
•
Kim, Young Jae
•
Chang, Ki Sung
•
Ahn, Min Cheol
•
Park, Dong Keun
Date Issued
July 2009
Journal
IEEE Transactions on Applied Superconductivity
Publisher
Institute of Electrical and Electronics Engineers
Citation
Dong Keun Park et al. “Analytical and Experimental Studies on the Hybrid Fault Current Limiter Employing Asymmetric Non-Inductive Coil and Fast Switch.” Applied Superconductivity, IEEE Transactions on 19.3 (2009): 1896-1899. © 2009 Institute of Electrical and Electronics Engineers
Version
Final published version
Abstract
This paper deals with design and operating test of a novel hybrid FCL. The FCL system consists of a coil, a fast switch and a resistor for bypassing the fault current. The switch is driven by novel non-inductive coil suggested in this paper but an extra driving coil is required for fast switch in existing hybrid FCL. We used two kinds of HTS wire for the coil. The impedance of the coil was negligible in normal operation. But different quench characteristics of HTS wires caused asymmetric current distribution which induced effective magnetic flux in the coil during faults. The switch was opened by repulsive force from this magnetic flux in fast response to the fault. Then, all current were flew through the normal conductive bypass resistor connected in parallel to both the coil and the switch. Electromagnetic analysis of the coil based on finite element method was performed. Also, a small-scale asymmetric non-inductive coil was designed, fabricated and tested. The proposed hybrid FCL system showed fast and efficient current limiting characteristic.
Subjects
superconducting fault current limiter
non-inductive coil
hybrid SFCL
fast switch
asymmetric coil
MIT Department
Francis Bitter Magnet Laboratory (Massachusetts Institute of Technology)
Terms of Use
Article is made available in accordance with the publisher's policy and may be subject to US copyright law. Please refer to the publisher's site for terms of use.
Persistent DSpace Link
http://hdl.handle.net/1721.1/53514
DOI of Published Version
http://dx.doi.org/10.1109/tasc.2009.2018069
Repository logo
PrivacyPermissionsAccessibilityContact us
Repository logo
Notify us about copyright concerns.