dc.descriptionThesis: S.M. in Building Technology, Massachusetts Institute of Technology, Department of Architecture, September, September, 2020en_US
dc.descriptionCataloged from the official PDF of thesis.en_US
dc.descriptionIncludes bibliographical references (pages 101-102).en_US
dc.description.abstractThe Boston climate is known for its long, cold winters but it also suffers from hot, humid summers. The dehumidification needed to maintain occupant comfort in summer is often provided by condensing the excess moisture onto surfaces cooled by cold water. The systems currently used to provide the cold water have limited efficiencies, so alternative systems must be sought in order to achieve reductions in building energy use and to reduce the rate of climate change. This research examines the feasibility of a ground-cooling storage system that stores the abundant Boston winter cold in an underground block of soil to provide dehumidification in summer. In winter, heat exchangers use the cold air to produce cold water, which flows through a set of pipes in the soil block, cooling the soil. In summer, the cooling stored in the soil block is used to provide cold water for the dehumidifier, thus meeting the latent cooling loads of the building. The physical scale of the system required was found to be reasonable, relative to typical building sizes. The soil block, which does not use any valuable program space, was sized as less than 10% of the overall building size and did not require deep excavation. Winter thermal modeling showed that the soil block could be fully charged in a typical winter season. The summer thermal modeling showed that the system can meet the majority of the building cooling loads and is capable of responding to cooling peaks. The system energy use is primarily driven by the use of the heat exchangers for winter charging. The system was estimated to have a coefficient of performance of 71, which is much higher than that of comparable systems used for dehumidification. In conclusion, this feasibility study found that the proposed system shows promising results as an alternative to conventional systems and is worth further investigation.en_US
dc.description.statementofresponsibilityby Nicole Tang Liwen.en_US
dc.format.extent119 pagesen_US
dc.language.isoengen_US
dc.publisherMassachusetts Institute of Technologyen_US
dc.rightsMIT theses may be protected by copyright. Please reuse MIT thesis content according to the MIT Libraries Permissions Policy, which is available through the URL provided.en_US
dc.rights.urihttp://dspace.mit.edu/handle/1721.1/7582en_US
dc.subjectArchitecture.en_US
dc.titleExamining the feasibility of a novel ground-storage cooling systemen_US
dc.typeThesisen_US
dc.description.degreeS.M. in Building Technologyen_US
dc.contributor.departmentMassachusetts Institute of Technology. Department of Architectureen_US
dc.identifier.oclc1288614596en_US
dc.description.collectionS.M. in Building Technology Massachusetts Institute of Technology, Department of Architectureen_US
dspace.imported2021-12-17T18:24:06Zen_US
mit.thesis.degreeMasteren_US
mit.thesis.departmentArchen_US


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record