Show simple item record

dc.contributor.advisorLeslie K. Norford.en_US
dc.contributor.authorSu, Po-An (Po-An Leo)en_US
dc.contributor.otherMassachusetts Institute of Technology. Department of Architecture.en_US
dc.date.accessioned2015-10-14T15:04:40Z
dc.date.available2015-10-14T15:04:40Z
dc.date.copyright2015en_US
dc.date.issued2015en_US
dc.identifier.urihttp://hdl.handle.net/1721.1/99306
dc.descriptionThesis: S.M. in Building Technology, Massachusetts Institute of Technology, Department of Architecture, 2015.en_US
dc.descriptionCataloged from student-submitted PDF version of thesis.en_US
dc.descriptionIncludes bibliographical references (pages 74-77).en_US
dc.description.abstractSecondary frequency regulation is a necessary electric grid ancillary service that balances electric power system supply and demand on short time intervals of seconds to minutes. Commercial HVAC chillers may be well positioned to provide secondary frequency regulation as a demand side resource. Commercial 200 ton (703 kWth) chillers serving two buildings in the Boston area are used to experimentally develop a practical closed-loop controller that modifies chiller power demand to provide secondary frequency regulation. In the first setup, a physical controller is connected directly to the chiller and adjusts power through chilled water setpoint. In the second setup, both the chiller and air handling units are controlled through the BAS. Demonstrations using standard electric system operator test routines show the chiller power response to exceed qualification requirements while providing up to +/-25% of chiller nameplate power in secondary frequency regulation capability. The controller is further demonstrated to provide secondary frequency regulation continuously for several hours longer than the standard test routines, during which building cooling load changes significantly. Analysis of results indicate minimum power and variable COP as two factors that could be incorporated into future models to more accurately reflect observed chiller transient behaviour and predict performance. BAS communication delays, ramp rate limits, and compressor cycling are additional factors that can have significant negative impacts on controller performance. Extrapolation of experiment results to higher-level analysis indicates that chillers can contribute to the secondary frequency regulation requirements at the grid level in aggregate, although potential varies greatly depending on climate and building type. There is more potential in the south, where 21% of secondary frequency regulation requirements might be met with chillers; the contribution of chillers in colder climates is minimal. Short-term power balance to achieve stability is essential for the operation of the modern electrical power system. Providing stability through modified control of existing HVAC chillers in commercial buildings is a technologically feasible alternative to existing solutions and can make a meaningful contribution to the electrical grid.en_US
dc.description.statementofresponsibilityby Po-An (Leo) Su.en_US
dc.format.extent92 pagesen_US
dc.language.isoengen_US
dc.publisherMassachusetts Institute of Technologyen_US
dc.rightsM.I.T. theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. See provided URL for inquiries about permission.en_US
dc.rights.urihttp://dspace.mit.edu/handle/1721.1/7582en_US
dc.subjectArchitecture.en_US
dc.titleDemonstration of HVAC chiller control for power grid frequency regulationen_US
dc.title.alternativeDemonstration of heating, ventilation and air conditioning chiller control for power grid frequency regulationen_US
dc.typeThesisen_US
dc.description.degreeS.M. in Building Technologyen_US
dc.contributor.departmentMassachusetts Institute of Technology. Department of Architecture
dc.identifier.oclc922935865en_US