Heat transfer and pressure drop data for high heat flux densities to water at high subcritical pressures
Author(s)
Rohsenow, Warren M.; Clark, John A.
DownloadHTL_TR_1951_003.pdf (9.231Mb)
Other Contributors
Massachusetts Institute of Technology. Division of Industrial Cooperation.
Massachusetts Institute of Technology. Heat Transfer Laboratory.
Metadata
Show full item recordAbstract
Local surface ooeffioients of heat t-ansfer, overall pressure drop data and mean friction factor are presented for heat flamms up to 3.52106 BtuAr ft2 for water flowing in a nickel tabe isder the following conditions: mass rates of flow up to 5.6x 106 lb.m/hr ft2 (or inlet velocities up to 30 ft/sec), absolute pressures up to 2000 pula, and liquid suboooling between 50 F and 250 T. The test section dmnsins were 0.160 inoh I.D. and 9.4 inches long.
Date issued
1951Publisher
Cambridge, Mass. : M.I.T. Division of Industrial Cooperation, 1951
Other identifiers
14871670
Series/Report no.
Technical report (Massachusetts Institute of Technology, Heat Transfer Laboratory) ; no. 3.
Keywords
Heat -- Transmission., Pressure.