A Retrofit 60 Hz Current Sensor for Power Monitoring at the Circuit Breaker Panel

Author(s)
Cooley, John J.; Vickery, Daniel R.; Avestruz, Al-Thaddeus; Clifford, Zachary; Leeb, Steven B.
Thumbnail
DownloadLeeb_A retrofit 60 Hz.pdf (956.5Kb)
PUBLISHER_POLICY

Publisher Policy

Article is made available in accordance with the publisher's policy and may be subject to US copyright law. Please refer to the publisher's site for terms of use.

Terms of use
Article is made available in accordance with the publisher's policy and may be subject to US copyright law. Please refer to the publisher's site for terms of use.
Metadata
Show full item record
Abstract
Improved signal conditioning electronics and new experimental results are presented for a sensor that measures current flow in a circuit breaker. A PIC microcontroller optimizes the phase reference for the synchronous detection system on startup eliminating the need for I/Q demodulation. Ultimately, the parts count of the signal conditioning electronics is halved compared to the previous work. Experimental results are presented demonstrating the sensor's response to 60 Hz signals with higher harmonic content and to step transients in 60 Hz signal amplitudes. The proposed current sensor does not require permanent modification of the breaker panel or the circuit breaker itself. The intent of this work is to develop a low-cost, non-intrusive, retrofit sensor for centralized power monitoring at the circuit breaker.
Date issued
2010-09
URI
http://hdl.handle.net/1721.1/72946
Department
Massachusetts Institute of Technology. Department of Electrical Engineering and Computer Science
Journal
Proceedings of the IEEE 12th Workshop on Control and Modeling for Power Electronics (COMPEL), 2010
Publisher
Institute of Electrical and Electronics Engineers (IEEE)
Citation
Cooley, John J. et al. “A Retrofit 60 Hz Current Sensor for Power Monitoring at the Circuit Breaker Panel.” Proceedings of the IEEE 12th Workshop on Control and Modeling for Power Electronics (COMPEL), 2010. 1–7.
Version: Final published version
ISBN
978-1-4244-7461-5
978-1-4244-7462-2

Collections
  • MIT Open Access Articles

Browse

All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

My Account

Login

Statistics

OA StatisticsStatistics by CountryStatistics by Department
MIT Libraries
PrivacyPermissionsAccessibilityContact us
MIT
Content created by the MIT Libraries, CC BY-NC unless otherwise noted. Notify us about copyright concerns.