Show simple item record

dc.contributor.authorRay, Stephen D.
dc.contributor.authorFukuda, Masashi
dc.contributor.authorMenchaca-Brandan, Maria-Alejandra
dc.contributor.authorHasegawa, Iwao
dc.contributor.authorGlicksman, Leon R.
dc.contributor.authorOchiai, Natsuko
dc.date.accessioned2015-07-15T14:31:20Z
dc.date.available2015-07-15T14:31:20Z
dc.date.issued2013
dc.identifier.isbn9781936504541
dc.identifier.issn0001-2505
dc.identifier.urihttp://hdl.handle.net/1721.1/97745
dc.description.abstractMix-mode or hybrid ventilation systems have been previously shown to reduce cooling and ventilation energy consumption. This paper presents a case study of a new ten story 83,700 ft² (7,780 m²) office building in downtown Tokyo with a hybrid ventilation system that uses only 1.7% of the building footprint for ventilation shafts. The control system design is presented as an example of balancing the comfort expectations of multiple tenants in a mix-mode system. On-site measurements are presented from a three week commissioning project to show: modest temperature differences within the occupied zone with a maximum difference of 1.5 °F (0.83 °C), large differences of up to 6.1 °F (3.4 °C) between the measured outdoor temperature in the control system and the actual inlet temperature for the natural ventilation system, the importance of smooth integration of various design teams, and the use of low-power fans, 1.2-0.60 hp (900-450 W), that leverage the low pressure drop through the building when natural driving forces are insufficient for pure natural ventilation. Practical lessons learned from the design and commissioning of the building are also shared.en_US
dc.description.sponsorshipHulic Co., Ltd.en_US
dc.language.isoen_US
dc.publisherAmerican Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE)en_US
dc.rightsCreative Commons Attribution-Noncommercial-Share Alikeen_US
dc.rights.urihttp://creativecommons.org/licenses/by-nc-sa/4.0/en_US
dc.sourceGlicksmanen_US
dc.titleOverview of Hybrid Ventilation Control System and Full Scale Monitoringen_US
dc.typeArticleen_US
dc.identifier.citationRay, Stephen D., Masashi Fukuda, Maria-Alejandra Menchaca-Brandan, Iwao Hasegawa, Leon R. Glicksman, and Natsuko Ochiai. "Overview of Hybrid Ventilation Control System and Full Scale Monitoring." ASHRAE Transactions. 2013, Vol. 119 Issue 2, 1-8.en_US
dc.contributor.departmentMassachusetts Institute of Technology. Building Technology Groupen_US
dc.contributor.departmentMassachusetts Institute of Technology. Department of Architectureen_US
dc.contributor.departmentMassachusetts Institute of Technology. Department of Mechanical Engineeringen_US
dc.contributor.mitauthorRay, Stephen D.en_US
dc.contributor.mitauthorGlicksman, Leon R.en_US
dc.relation.journalASHRAE Transactionsen_US
dc.eprint.versionAuthor's final manuscripten_US
dc.type.urihttp://purl.org/eprint/type/ConferencePaperen_US
eprint.statushttp://purl.org/eprint/status/NonPeerRevieweden_US
dspace.orderedauthorsRay, Stephen D.; Fukuda, Masashi; Menchaca-Brandan, Maria-Alejandra; Hasegawa, Iwao; Glicksman, Leon R.; Ochiai, Natsukoen_US
mit.licenseOPEN_ACCESS_POLICYen_US
mit.metadata.statusComplete


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record